Do you have any questions about the product?
We will be happy to answer them in messengers
Motor (output) choke 490A, 380V, 220 kW, 0.014 mH (OCL-0490-014U-0.4SA)
Do you have any questions about the product?
We will be happy to answer them in messengers
≈ 250 UAH / Free for orders over 5,000 UAH
≈ 350 UAH / Free for orders over 5,000 UAH
Free
Technical specifications
Description
Three-phase motor choke 490A, 380V, 220 kW, 0.014 mH OCL-0490-014U-0.4SA are installed at the output of a frequency converter to filter the current supplied to three-phase electric motors at 380 V. The purpose of the output electric choke is as follows:
- Creating inductive resistance that limits the power supply current to the motor, thus preventing overload and damage;
- Preventing sudden current surges during motor start-up, which can lead to equipment failure;
- Clearing the current sine wave from unwanted high harmonics (high-frequency noises) arising in the drive.
Use an AC output choke in the circuit between the frequency converter and the asynchronous electric motor to improve the quality of the drive's power supply, as well as ensure safe and long-term equipment operation.
Technical specifications of motor output choke OCL-0490-014U-0.4SA
| Operating Voltage | 3 phases 380 V |
|---|---|
| Voltage Drop | 1% for 380 V (less than 4%) |
| Operating Frequency | 50/60 Hz |
| Operating Current | 490 A |
| Maximum Current | may exceed operating no more than 150% for 60 s |
| Inductance | 0.014 mH |
| Insulation Class | F, H |
| Protection Class | IP00 - IP22 |
| Noise | ≤65 dB |
| Temperature Rise | ≤85 K |
| Dielectric Strength | AC 3000 V/50 Hz/5 mA/10 s |
| Insulation Resistance | 100 VDC, ≤100 MΩ |
| Ambient Operating Temperature | -25 ~ +45℃ |
Operating Conditions of Motor Choke (Line Reactor) OCL-0490-014U-0.4SA
- In the temperature range from minus 10 to 45℃ the choke's nominal parameters are tabulated. At temperatures above 55℃, the nominal current decreases by approximately 2% for each additional +1℃.
- Altitude should not exceed 2000 m above sea level.
- Humidity less than 90%.
- Environment: free from harmful gases, flammable items, with good ventilation present.
When placing the choke in a cabinet, ensure ventilation for adequate equipment cooling.
Reviews (0)
based on 0 reviews
Average rating of our customers