Mon-Fri from 9:00 to 18:00
Sat-Sun Closed
Contact us
Catalog
Main menu
Catalog

Do you have any questions about the product?
We will be happy to answer them in messengers

Motor (output) choke 5A, 380V, 1.5 kW, 1.4 mH (OCL-0005-1M40-0.4SC)

In Stock In Stock
Product Code:
SPLC-OCL-0005-1M40-0.4SC
Brand:
Specialist
3 654,00 UAH
Qty:

Do you have any questions about the product?
We will be happy to answer them in messengers

Delivery of goods
More details
New Post Office and address
New Post Office and address

≈ 250 UAH / Free for orders over 5,000 UAH

2-4 days
By courier in Ukraine
By courier in Ukraine

≈ 350 UAH / Free for orders over 5,000 UAH

1-2 days
Pickup from our warehouse
Pickup from our warehouse

Free

Today, after 2:00 PM
Payment
More details
Visa Mastercard Liqpay Monobank

Technical specifications

Delivery time
60 днів

Description

Three-phase Motor Reactor 5A, 380V, 1.5 kW, 1.4 mH OCL-0005-1M40-0.4SC is installed at the output of a frequency converter for filtering the current supplied to three-phase electric motors 380V. The purpose of the output reactor is as follows:

  • Creating inductive resistance which limits the motor supply current, thus preventing overload and damage;
  • Preventing sharp current surges during motor start, which could damage the equipment;
  • Cleaning the current sine wave from undesirable high harmonics (high-frequency noises) occurring in the drive.

Use the AC output reactor in the circuit between the frequency converter and the asynchronous electric motor to improve the quality of the drive power supply, as well as for safe and prolonged equipment operation.

Technical Specifications of Motor Output Reactor OCL-0005-1M40-0.4SC
Working Voltage 3 Phases 380 V
Voltage Drop 1% for 380V (less than 4%)
Operating Frequency 50/60 Hz
Operating Current 5 A
Maximum Current may exceed operating by no more than 150% for 60s
Inductance 1.4 mH
Insulation Class F, H
Protection Class IP00 - IP22
Noise ≤65 dB
Temperature Rise ≤85 k
Dielectric Strength AC 3000 V/50 Hz/5 mA/10 s
Insulation Resistance 100 VDC, ≤100 MΩ
Ambient Operating Temperature -25 ~ +45℃
Operating Conditions of Motor Reactor (Line Reactor) OCL-0005-1M40-0.4SC
  • In the temperature range from minus 10 to 45℃, the nominal parameters of the reactor are tabular. At a temperature above 55℃, the nominal current decreases by about 2% for each extra +1℃.
  • Altitude should not exceed 2000 m above sea level.
  • Air humidity should be below 90%.
  • Environment: free of harmful gases, flammable objects, with good ventilation.

When placing the reactor in a cabinet, ensure ventilation for ample cooling of the equipment.