Do you have any questions about the product?
We will be happy to answer them in messengers
Motor (output) choke 30A, 380V, 11 kW, 0.23 mH (OCL-0030-0M23-0.4SC)
Do you have any questions about the product?
We will be happy to answer them in messengers
≈ 250 UAH / Free for orders over 5,000 UAH
≈ 350 UAH / Free for orders over 5,000 UAH
Free
Technical specifications
Description
Three-phase motor choke 30A, 380V, 11 kW, 0.23 mH OCL-0030-0M23-0.4SC is installed at the output of the frequency converter to filter the current supplied to three-phase electric motors 380 V. The purpose of the output electric choke is as follows:
- Creation of inductive resistance that limits the motor power current and thus prevents its overload and damage;
- Prevention of sharp current surges during the motor's start-up, which may lead to equipment failure;
- Cleaning the current sine wave from unwanted high harmonics (high-frequency noise) occurring in the electric drive.
Use the AC output choke in the circuit between the frequency converter and the asynchronous electric motor to improve the power quality of the drive, as well as ensure safe and long-lasting equipment operation.
Technical characteristics of the motor output choke OCL-0030-0M23-0.4SC
| Operating voltage | 3 phases 380 V |
|---|---|
| Voltage drop | 1% for 380 V (less than 4%) |
| Operating frequency | 50/60 Hz |
| Operating current | 30 A |
| Maximum current | may exceed operating by no more than 150% for 60 s |
| Inductance | 0.23 mH |
| Insulation class | F, H |
| Protection class | IP00 - IP22 |
| Noise | ≤65 dB |
| Temperature rise | ≤85 k |
| Dielectric strength | AC 3000 V/50 Hz/5 mA/10 s |
| Insulation resistance | 100 VDC, ≤100 MΩ |
| Ambient operating temperature | -25 ~ +45℃ |
Operating conditions of the motor choke (line reactor) OCL-0030-0M23-0.4SC
- In the temperature range from minus 10 to 45℃ the rated parameters of the choke are tabular. At temperatures above 55℃, the rated current decreases by approximately 2% for every additional +1℃.
- Altitude should not exceed 2000 m above sea level.
- Air humidity less than 90%.
- Environment: free from harmful gases, flammable objects, well ventilated.
When placing the choke in a cabinet, ensure ventilation for adequate equipment cooling.
Reviews (0)
based on 0 reviews
Average rating of our customers