Do you have any questions about the product?
We will be happy to answer them in messengers
Motor (output) choke 330A, 380V, 160 kW, 0.021 mH (OCL-0330-021U-0.4SA)
Do you have any questions about the product?
We will be happy to answer them in messengers
≈ 250 UAH / Free for orders over 5,000 UAH
≈ 350 UAH / Free for orders over 5,000 UAH
Free
Technical specifications
Description
Three-phase Motor Output Choke 330A, 380V, 160 kW, 0.021 mH OCL-0330-021U-0.4SA is installed at the output of the frequency converter to filter the current supplied to the three-phase electric motors 380V. The purpose of the output electrical choke is as follows:
- Creating inductive resistance that limits the motor's power current and thereby prevents overload and damage;
- Preventing abrupt current surges during the motor start-up, which can lead to equipment failure;
- Cleaning the current sinusoid from unwanted high harmonics (high-frequency noise) occurring in the drive.
Use the AC output choke in the circuit between the frequency converter and the asynchronous motor to improve the power quality of the drive, as well as secure and long-lasting equipment operation.
Technical Specifications of the Motor Output Choke OCL-0330-021U-0.4SA
| Operating Voltage | 3 phases 380 V |
|---|---|
| Voltage Drop | 1% for 380V (less than 4%) |
| Operating Frequency | 50/60 Hz |
| Operating Current | 330 A |
| Maximum Current | may exceed operating current by no more than 150% for 60 s |
| Inductance | 0.021 mH |
| Insulation Class | F, H |
| Protection Class | IP00 - IP22 |
| Noise | ≤65 dB |
| Temperature Rise | ≤85 K |
| Dielectric Strength | AC 3000 V/50 Hz/5 mA/10 s |
| Insulation Resistance | 100 VDC, ≤100 MOhm |
| Operating Environment Temperature | -25 ~ +45℃ |
Operating Conditions of Motor Choke (Line Reactor) OCL-0330-021U-0.4SA
- In the temperature range from minus 10 to 45℃, the rated parameters of the choke are tabular. At temperatures above 55℃, the nominal current decreases by approximately 2% for each additional +1℃.
- Altitude should not exceed 2000 m above sea level.
- Humidity less than 90%.
- Environment: no harmful gases, flammable objects, presence of good ventilation.
When placing the choke in a cabinet, ensure ventilation for sufficient cooling of the equipment.
Reviews (0)
based on 0 reviews
Average rating of our customers