Do you have any questions about the product?
We will be happy to answer them in messengers
Motor (output) choke 600A, 380V, 280 kW, 0.012 mH (OCL-0600-012U-0.4SA)
Do you have any questions about the product?
We will be happy to answer them in messengers
≈ 250 UAH / Free for orders over 5,000 UAH
≈ 350 UAH / Free for orders over 5,000 UAH
Free
Technical specifications
Description
Three-phase Motor Choke 600A, 380V, 280 kW, 0.012 mH OCL-0600-012U-0.4SA is installed at the output of the frequency converter to filter the current supplied to 380 V three-phase electric motors. The purpose of the output electric choke is as follows:
- Creation of inductive resistance that limits the motor's power supply current, thus preventing overload and damage;
- Prevention of sharp current spikes during motor startup that may cause equipment failure;
- Cleansing the current waveform from unwanted high harmonics (high-frequency noise) inherent in electric drives.
Use the AC output choke in the circuit between the frequency converter and the asynchronous motor to enhance the power supply quality of the drive, as well as to ensure safe and long-term operation of the equipment.
Technical Specifications of the Motor Output Choke OCL-0600-012U-0.4SA
| Operating Voltage | 3 Phases 380 V |
|---|---|
| Voltage Drop | 1% for 380 V (less than 4%) |
| Operating Frequency | 50/60 Hz |
| Operating Current | 600 A |
| Maximum Current | may exceed operating by no more than 150% for 60 s |
| Inductance | 0.012 mH |
| Insulation Class | F, H |
| Protection Class | IP00 - IP22 |
| Noise | ≤65 dB |
| Temperature Rise | ≤85 K |
| Dielectric Strength | AC 3000 V/50 Hz/5 mA/10 s |
| Insulation Resistance | 100 VDC, ≤100 MΩ |
| Operating Ambient Temperature | -25 ~ +45℃ |
Operating Conditions for the Motor Choke (Line Reactor) OCL-0600-012U-0.4SA
- At temperature ranges from minus 10 to 45℃, choke ratings are tabular. When temperature exceeds 55℃, the rated current decreases by approximately 2% for each additional +1℃.
- Altitude not exceeding 2000 m above sea level.
- Air humidity less than 90%.
- Environment: free from harmful gases, flammable items, presence of good ventilation.
When placing the choke in a cabinet, ensure ventilation for adequate cooling of the equipment.